Title :
Impedance type main protection for large capacity ultra high voltage transformers
Author :
He Jaili ; Wang Guoxin ; He Jihong ; Li Bin
Author_Institution :
Eelectric Power Dept., Tianjin Univ., Tianjin, China
Abstract :
The large capacity power equipment should be equipped by absolutely independent duplicated main protections. For large capacity generators there are several main protections of different principle can be used. But for large capacity transformers only longitudinal current differential protection principle was used as main protection till now. It is seriously affected by the magnetizing inrush currents especially for large capacity UHV transformers. In this paper an impedance type main protection principle for large capacity UHV transformers is proposed. The construction of protection scheme of this principle, the ability to withstand magnetizing inrush currents, the reliability and the sensitivity of its operation are studied. Theoretical analysis and digital simulations proved the effectiveness and advantages of this main protection principle for large capacity UHV transformers.
Keywords :
potential transformers; power transformer protection; impedance type main protection; inrush currents; large capacity generators; large capacity power equipment; large capacity ultra high voltage transformers; Current measurement; Impedance; Logic gates; Substations; Surge protection; Surges; Windings; Impedance protection; Transformer protection; UHV transmission;
Conference_Titel :
Advanced Power System Automation and Protection (APAP), 2011 International Conference on
Conference_Location :
Beijing
Print_ISBN :
978-1-4244-9622-8
DOI :
10.1109/APAP.2011.6180787