    A static dynamometer for load testing large variable frequency motor drives

  • Author

    Sueker, K.H.

  • Author_Institution
    110 Garlow Drive, Pittsburgh, PA, USA
  • fYear
    1997
  • Abstract
    The static dynamometer, an apparent oxymoron, is a system which allows full load testing of variable frequency motor drives with no rotating equipment and only minimal demand from the power line. By inserting a reactor between the drive output and the line from which it is powered, the drive can be made to appear as a synchronous generator. This arrangement offers a practical alternative to the motor-generator sets usually employed for load testing. The required equipment consists of a set of power reactors approximating 10% of the drive rating, a contactor and a phase locked loop circuit for regulating the drive phase relative to the line. The static dynamometer is in production use on variable speed drives from 20 to 5000 hp and 480 to 4160 V. There are no intrinsic limits to either power or voltage for its application
  • Keywords
    dynamometers; machine testing; motor drives; variable speed drives; 20 to 5000 hp; 480 to 4160 V; drive rating; load testing; motor-generator sets; phase locked loop circuit; power reactors; production experience; static dynamometer; synchronous generator; variable frequency motor drives; variable speed drives; Circuit testing; Frequency; Inductors; Motor drives; Phase locked loops; Production; Synchronous generators; System testing; Variable speed drives; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Machines and Drives Conference Record, 1997. IEEE International
  • Conference_Location
    Milwaukee, WI
  • Print_ISBN
    0-7803-3946-0
  • Type

    conf

  • DOI
    10.1109/IEMDC.1997.604303
  • Filename
    604303