Simulation of MV distribution networks with asynchronous local generation sources
Author
Lopes, J. A Peqs ; Maciel Barbosa, F.P. ; Pidre, J. Cidras
fYear
1991
Firstpage
1453
Abstract
Operation problems that result from MV distribution networks with local asynchronous generation sources connected are examined. In order to analyze steady-state operating situations, a load-flow calculation must be performed. The presence of asynchronous generators imposes the adoption of a consistent bus modelization using a new bus type, the PX bus, where P is the active generated power and X is a nonlinear magnetizing reactance. This approach introduces some modifications in the conventional load-flow algorithms, thereby increasing the total number of iterations
Keywords
asynchronous generators; digital simulation; distribution networks; load flow; power engineering computing; MV distribution networks; active generated power; asynchronous local generation sources; load-flow calculation; nonlinear magnetizing reactance; steady-state operating situations; Cogeneration; Induction generators; Load flow analysis; Performance analysis; Power generation; Power system modeling; Production; Substations; System testing; Voltage;
fLanguage
English