DocumentCode
1711152
Title
Application of Pre-Shutdown AC Voltage Test System for XLPE Power Cable
Author
Lee, C.Y. ; Chang, S.H. ; Baek, S.K. ; Kwon, S.T. ; Kim, D.W.
Author_Institution
Dept. of Electr. Eng., Busan Nat. Univ., Busan
fYear
2006
Firstpage
1
Lastpage
6
Abstract
This study deals with pre-shutdown test system in AC withstand voltage test for XLPE power cable, which is able to minimize electrical damage enough to investigate source of defects with naked eye when electrical breakdown is happened. Principle of this system is based on high speed shutdown of the test voltage just before the electrical breakdown by PBD system combined with time domain reflection (TDR) method of partial discharge. By experiments with model cables having artificial defects, its working abilities, such as shutdown speed and accuracy as well as operating condition were investigated. Through the test result of power cables with unknown defect, it was proven that this pre- shutdown AC voltage test system was successfully worked in the AC voltage test for power cable.
Keywords
electric breakdown; partial discharges; power cable testing; XLPE power cable; electrical breakdown; partial discharge; pre-shutdown AC voltage test system; time domain reflection method; AC generators; Breakdown voltage; Cable insulation; Circuit testing; Dielectrics and electrical insulation; Electric breakdown; Insulation testing; Partial discharges; Power cables; System testing; Breakdown; Insulation; Partial discharge; Power Cable;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology, 2006. PowerCon 2006. International Conference on
Conference_Location
Chongqing
Print_ISBN
1-4244-0110-0
Electronic_ISBN
1-4244-0111-9
Type
conf
DOI
10.1109/ICPST.2006.321530
Filename
4116334
Link To Document