DocumentCode :
1711694
Title :
A New Under-Frequency Load Shedding Scheme Considering Load Frequency Characteristics
Author :
Xiong, Xiaofu ; Li, Wenyuan
Author_Institution :
Electr. Eng. Coll., Key Lab. of High Voltage Eng. & Electr. New Technol., Chongqing Univ., Chongqing
fYear :
2006
Firstpage :
1
Lastpage :
4
Abstract :
A new method of optimizing under-frequency load shedding (UFLS) is developed in the paper. The main idea is that with the online measurement information of the loads and load-frequency regulation factors, loads with smaller frequency regulation factors are shed earlier than those with larger frequency regulation factors. Therefore the power absorbed by loads will be more effectively decreased and the power balance will be achieved more quickly in the transient process. The implementation method and digital simulation of the proposed scheme are presented.
Keywords :
power system measurement; load frequency characteristics; load-frequency regulation factors; online load measurement information; power balance; transient process; under-frequency load shedding scheme; Accidents; Equations; Frequency control; Frequency measurement; Power system measurements; Power system protection; Power system restoration; Power system security; Power system transients; Voltage; Frequency regulation factor; Load-frequency characteristics; Power system; Under-frequency load shedding (UFLS);
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power System Technology, 2006. PowerCon 2006. International Conference on
Conference_Location :
Chongqing
Print_ISBN :
1-4244-0110-0
Electronic_ISBN :
1-4244-0111-9
Type :
conf
DOI :
10.1109/ICPST.2006.321582
Filename :
4116351
Link To Document :
بازگشت