Abstract
Characteristic of traction loads as well as aging mechanism of insulation is analyzed. Then computer simulation about temperature of winding is achieved. Based on results, a new experimental system is designed to study the relationship between insulating aging and traction loads. The gases dissolved in oil (GDO) of experiment transformer such as CO and CO2 is monitored and analyzed. The affect of thermal surge on insulation aging is studied through comparing the GDO of transformer under surge loads and equivalent loads. Test results show that the traction loads seriously affect insulation aging and loss-of-life of traction transformer, which should not be neglected.
Keywords
ageing; carbon compounds; chemical analysis; insulation testing; power transformer insulation; power transformer testing; surges; thermal insulating materials; traction power supplies; transformer oil; transformer windings; CO; CO2; computer simulation; gases dissolved; insulation aging mechanism; loss-of-life; oil; thermal surge; traction load characteristic; transformer; winding temperature; Aging; Computer simulation; Computerized monitoring; Dissolved gas analysis; Gases; Oil insulation; Petroleum; Power transformer insulation; Surges; Temperature;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulating Materials, 2005. (ISEIM 2005). Proceedings of 2005 International Symposium on
Print_ISBN
4-88686-063-X
Type
conf
DOI
10.1109/ISEIM.2005.193594
Filename
1496194
Link To Document