A new generation of medium voltage vacuum circuit breakers were used to retrofit sealed Sf6 contactors which experienced difficulty in disconnecting the loads safely after 15 years of service. The new breakers which replaced the contactors and the associated fuses were mounted on the same panel truck preserving all original interlocks. Mechanical and electrical modifications were implemented to match the new breakers to the existing panel. Retrofitted breakers are in good service successfully for 5 years now.
Keywords :
maintenance engineering; power stations; power system management; vacuum circuit breakers; medium voltage contactor; medium voltage vacuum circuit breaker; power station; retrofit implementation; retrofit sealed Sf6 contactor; Actuators; Circuit breakers; Coils; Contactors; Interrupters; Magnetic flux; Medium voltage; Power generation; Saturation magnetization; Springs; Magnetic actuator circuit breakers; Retrofit of medium voltage switchgear;