    Non-invasive discharge locator for overhead lines

  • Author

    Portugues, E. ; Moore, P.J.

  • Author_Institution
    Dept of Electron. & Electr. Eng., Bath Univ., UK
  • Volume
    3
  • fYear
    2005
  • Firstpage
    756
  • Abstract
    Electromagnetic interference caused by high voltage equipment such as partial discharges is well established and used within utilities to monitor the state of plant via periodic radio frequency interference (rfi) surveys. This paper describes investigations made by the authors into the location of a discharge source close to a domestic residence situated under a 132 kV overhead line. The owner of the residence had complained of interference to television and FM radio reception that was aggravated under dry conditions, often disappearing during rain. This situation has been inconclusively investigated prior to the study described here. Measurements were made that showed the interference was impulsive in nature. The impulses were used to precisely locate the partial discharge on the line. These results are then compared to those obtained from another overhead line where no complaints were received.
  • Keywords
    partial discharges; power overhead lines; radiofrequency interference; 132 kV; FM radio reception interference; domestic residence; electromagnetic interference; noninvasive discharge locator; overhead lines; partial discharges; radio frequency interference; television interference; Cameras; Circuit testing; Conductors; Electromagnetic interference; Fault location; Partial discharge measurement; Partial discharges; Radiofrequency interference; TV; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulating Materials, 2005. (ISEIM 2005). Proceedings of 2005 International Symposium on
  • Print_ISBN
    4-88686-063-X
  • Type

    conf

  • DOI
    10.1109/ISEIM.2005.193481
  • Filename
    1496285