• DocumentCode
    1716151
  • Title

    Return voltage measurements - the step from experimental data to a relevant diagnostic interpretation

  • Author

    Patsch, Rainer ; Kouzmine, Oleg

  • Author_Institution
    Inst. of Mater. & Diagnostics in Electr. Eng., Siegen Univ., Germany
  • Volume
    3
  • fYear
    2005
  • Firstpage
    889
  • Abstract
    The condition of service aged medium voltage cables can be assessed by measuring the dielectric response of the insulation. In time domain this can be done via return voltage or/and depolarization current measurements. The paper deals with the interpretation of experimental results of return voltage measurements and discusses the relevance of different measurement conditions and the meaningfulness of the different diagnostic parameters chosen. Special emphasis is taken on the p-factor, a parameter that seems to be appropriate for all types of insulating materials.
  • Keywords
    insulating materials; power cable insulation; voltage measurement; depolarization current measurements; dielectric response measurement; insulating materials; insulation; p-factor; return voltage measurements; service aged medium voltage cables; Cable insulation; Cables; Circuits; Dielectric materials; Dielectric measurements; Dielectrics and electrical insulation; Electrodes; Polarization; Power transformer insulation; Voltage measurement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulating Materials, 2005. (ISEIM 2005). Proceedings of 2005 International Symposium on
  • Print_ISBN
    4-88686-063-X
  • Type

    conf

  • DOI
    10.1109/ISEIM.2005.193524
  • Filename
    1496329