• DocumentCode
    1716627
  • Title

    Adaptive control for the steam temperature of thermal power plants

  • Author

    Matsumura, S. ; Ogata, K. ; Fujii, S. ; Shioya, H.

  • Author_Institution
    Electr. Power & Dev. Center, Chuba Electr. Power Co. Inc., Nagoya, Japan
  • Volume
    2
  • fYear
    1998
  • Firstpage
    1105
  • Abstract
    An adaptive control system was applied to control the steam temperature of utility boilers. In the control system, an adaptive control strategy is embedded on the DCS controllers in parallel with each conventional PID controllers for the boiler. The authors have successfully implemented the proposed system at Chubu Electric Power´s Nishi-Nagoya No.3 unit and Owase-Mita No.l unit for controlling the main and reheat steam temperatures. The control improvement takes the form of reduced magnitude of temperature excursions caused by load changes, especially in the reheated steam temperature
  • Keywords
    adaptive control; boilers; control system synthesis; discrete time systems; steam power stations; temperature control; Chubu Electric Power; Nishi-Nagoya unit; Owase-Mita unit; adaptive control; discrete time systems; steam temperature; thermal power plants; utility boilers; Adaptive control; Boilers; Control systems; Error correction; Fuels; Furnaces; Power engineering and energy; Power generation; Temperature control; Three-term control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Control Applications, 1998. Proceedings of the 1998 IEEE International Conference on
  • Conference_Location
    Trieste
  • Print_ISBN
    0-7803-4104-X
  • Type

    conf

  • DOI
    10.1109/CCA.1998.721628
  • Filename
    721628