Title :
Lightning risk assessment evaluation on French nuclear power plants
Author :
Duqueroy, P. ; Miry, Celine ; Seltner, P.
Author_Institution :
R&D - Les Renardieres Labs., EDF (Electricite de France), Moret-sur-Loing, France
Abstract :
On one side, lightning risk assessment is carried out on French nuclear power plants since 2002. And on the other side, all kinds of incidents are collected since 1980. It is a good opportunity to evaluate the standardized risk assessment calculation with reality in that case. So we carried out calculation of all risk components on all structures of all sites and summarized the results to compare it with the real damage frequency between 1980 and 2012. It appears that a strict application of IEC 62305-2 hugely overestimate the damage frequency. We tried to analyze and understand the differences, and we proposed some evolutions to reach a satisfying adequacy between calculation and reality in the future.
Keywords :
IEC standards; lightning protection; nuclear power stations; risk analysis; French nuclear power plant; IEC 62305-2 application; damage frequency overestimation; lightning risk assessment evaluation; standardized risk assessment calculation; Grounding; Lightning; IEC 62305-2; Nuclear power plants; Risk assessment; Standards;
Conference_Titel :
Lightning Protection (ICLP), 2014 International Conference o
Conference_Location :
Shanghai
DOI :
10.1109/ICLP.2014.6973101