DocumentCode :
171893
Title :
Surge propagation and characteristics in building wiring systems
Author :
Xiang Luo ; Du, Yun ; Hongcai Chen
Author_Institution :
Dept. of Electr. Eng., Shanghai Jiaotong Univ., Shanghai, China
fYear :
2014
fDate :
11-18 Oct. 2014
Firstpage :
397
Lastpage :
401
Abstract :
This paper presents an experimental study of propagation characteristics of lightning surges in building wiring systems. Typical power cables or cable installations used for power distribution in buildings are selected for measurement. The influence of circuit branches and connected loads on the surges in systems is investigated as well. Finally surges measured in a large residential building are presented. It is found that surge impedance of power cables is generally lower than that of overhead lines. A significant reduction of surges is expected if the overhead line is terminated with an armored cable. Both circuit branch and connected loads can alter the waveform and amplitude of a surge significantly. This is further illustrated in the measurement of the surges conducted in a large residential building.
Keywords :
building management systems; lightning; lightning protection; power cables; surge protection; wiring; armored cable; building wiring systems; cable installations; circuit branches; connected loads; large residential building; lightning surges; overhead lines; power cables; power distribution; surge characteristics; surge impedance; surge propagation; surge reduction; Attenuation; Buildings; Cable TV; Impedance; Surges; Switches; Wiring; cable; distribution circuit; surge impedance; surge propogation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Lightning Protection (ICLP), 2014 International Conference o
Conference_Location :
Shanghai
Type :
conf
DOI :
10.1109/ICLP.2014.6973156
Filename :
6973156