DocumentCode
172042
Title
Lightning risk assessment method of transmission line using distributed traveling wave monitoring
Author
Lu Yong-ling ; Liu Yang ; Zhi-cheng Zhou ; Lei Meng-fei ; Chun Zhao ; En-ze Lu ; Jie Su
Author_Institution
Jiangsu Electr. Power Co. Res. Inst., Nanjing, China
fYear
2014
fDate
11-18 Oct. 2014
Firstpage
801
Lastpage
804
Abstract
Lightning current parameters, type and location of lightning fault are key factors for making a lightning risk assessment of transmission line scientifically. An assessment method is proposed on the basis of differentiated lightning protection ideology using distributed traveling wave monitoring, which treats lightning risk with more details and is employed in an actual 500kV transmission line. It is suggested that back striking risk is much higher than shield failure. Besides, the assessment result also provides guidance for lightning protection alteration in adopting measures.
Keywords
fault location; lightning protection; power transmission lines; power transmission protection; risk management; back striking risk; differentiated lightning protection ideology; distributed traveling wave monitoring; lightning fault location; lightning fault type; lightning protection alteration; lightning risk assessment method; shield failure; transmission line; voltage 500 kV; Electronic mail; Insulation; Lightning; Monitoring; Real-time systems; Security; Standards; differentiated lightning protection(DLP); distributed traveling wave monitoring(DTWM); lightning risk assessment; lightning trip-out; transmission line;
fLanguage
English
Publisher
ieee
Conference_Titel
Lightning Protection (ICLP), 2014 International Conference o
Conference_Location
Shanghai
Type
conf
DOI
10.1109/ICLP.2014.6973232
Filename
6973232
Link To Document