DocumentCode
172083
Title
Improvement of protection system against wire break caused by lightning overvoltage in DC traction system
Author
Shibata, Naotaka ; Morimoto, Hiroaki ; Yoshii, Tsurugi ; Uematsu, Syouji ; Hayashiya, Hitoshi
Author_Institution
Power Supply Technol. Div., Railway Tech. Res. Inst., Tokyo, Japan
fYear
2014
fDate
11-18 Oct. 2014
Firstpage
1021
Lastpage
1026
Abstract
A novel protection system, consisting of protection wires and arcing horns. against wire break in DC traction system had been developed and examined. However, this system had a problem that arc current is not maintained stably at an arcing horn. The authors improved this system to solve the problem by adopting gapless protection devices instead of arcing horns. Examination results on a field test prove that this improved system can attain the desired purpose.
Keywords
lightning protection; overvoltage protection; traction; DC traction system; arcing horns; gapless protection devices; lightning overvoltage; protection system; wire break; Arresters; Earth; Limiting; Resistors; Substations; Surges; DC traction system; metal-oxide varistor (MOV); protection device (PD); protection wire (PW); wire break;