DocumentCode :
1721964
Title :
Absorbent water battery set up in the vat of oil transformers
Author :
Rusu, Ioan
Author_Institution :
SC Electr. Serv SA, Romania
fYear :
2009
Firstpage :
1
Lastpage :
3
Abstract :
At oil transformer coils made by paper insulation, the present of water in paper lead to insulation demotion and electric faults. In the vat of transformers, at ambient temperature, the water migrates from oil in the isolation paper. The water in paper is distributed uniformly. At present times, for extracting the water from the isolate paper of coils conductors, with transformers in function, most used method consist in heating oil at 60-70 Celsius degrees, and after, when the water migrate from paper in oil, treating the oil to extract the water online in special installation outside the transformers. But, heating the oil at 60-70 Celsius degrees means to heat also the conductor´s isolation with the possibility to deteriorate the paper qualities. One solution for this problem could be to set up an absorbent water battery in the vat of transformers. So, the water inside the transformer will migrate in papers insulation coils but also in the absorbent water battery. If the quantity of coils paper is equal with the quantity on paper of battery, only 1/2 of water will migrate in paper insulation coils.
Keywords :
coils; paper; power transformer insulation; transformer oil; absorbent water battery; electric faults; installation; insulation demotion; oil transformers; paper insulation coils; vat; Batteries; Coils; Conductors; Dielectrics and electrical insulation; Electrical equipment industry; Oil insulation; Petroleum; Power transformer insulation; Temperature; Water heating; absorbent battery; insulation; paper; transformer; water;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
PowerTech, 2009 IEEE Bucharest
Conference_Location :
Bucharest
Print_ISBN :
978-1-4244-2234-0
Electronic_ISBN :
978-1-4244-2235-7
Type :
conf
DOI :
10.1109/PTC.2009.5282081
Filename :
5282081