Concept and practical testing of single pole operated earthing breakers in an urban MV cable network
Author :
Koeppl, Georg ; Abaecherli, Peter ; Schmid, Adrian ; Voss, Gerd
Author_Institution :
Koeppl Power Experts, Switzerland
fYear :
2005
Firstpage :
1
Lastpage :
4
Abstract :
The most important advantage of MV systems with isolated neutral or with Petersen coils is to allow uninterrupted power supply to the consumer in case of a single phase-to-ground fault even if it persists for a longer period. The shortcomings of those systems are: • possibly critical touch- and step voltages especially in larger systems with single phase-to-ground fault currents substantially higher than 100A • danger of double phase-to-ground faults caused by high transient voltages due to arc extinctions and restrikes at the fault location (intermittent faults) • possible destruction of the insulation of neighbouring cables by the fault current and transition to 2- and 3-phase faults.