• DocumentCode
    1723501
  • Title

    Charging tendency in transformer oil

  • Author

    Poovamma, P.K. ; Jagadish, R. ; Dwarakanath, K.

  • Author_Institution
    Central Power Res. Inst., Bangalore, India
  • fYear
    1992
  • Firstpage
    262
  • Lastpage
    267
  • Abstract
    Many failures in large forced-oil-cooled power transformers have been specifically attributed to static electrification, due to the flow of insulating oil. For this reason detailed investigations of some of the important parameters, such as flow rate, moisture content, temperature, extent of aging, and presence of copper, affecting the charging tendency of the oil have been carried out by employing a ministatic tester and a spinning disk system with paraffinic based oil. It is observed that the aforementioned parameters significantly influence the charging tendency of the oil
  • Keywords
    insulating oils; power transformers; static electrification; transformer insulation; charging tendency; extent of aging; flow of insulating oil; flow rate; forced-oil-cooled power transformers; moisture content; paraffinic based oil; static electrification; temperature; transformer oil; Aging; Copper; Moisture; Oil insulation; Petroleum; Power transformer insulation; Power transformers; Spinning; System testing; Temperature;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 1992. Annual Report. Conference on
  • Conference_Location
    Victoria, BC
  • Print_ISBN
    0-7803-0565-5
  • Type

    conf

  • DOI
    10.1109/CEIDP.1992.283178
  • Filename
    283178