Abstract :
In the paper new sensitive algorithms for detection of internal inter-turn faults in power transformers are described. Such faults are extremely difficult to detect since they induce negligible increase of the currents at the transformer terminals, although the currents flowing at the fault place are very high and dangerous for the transformer. The algorithms developed are based on the differential equation of the equivalent circuit of the transformer. In one version additional information from a CT installed inside of the triangle of delta side windings is used, which brings very promising results. Theoretical investigations are supported and illustrated with simulation studies performed with EMTP-ATP.
Keywords :
current transformers; differential equations; equivalent circuits; fault currents; fault diagnosis; power transformer protection; power transformer testing; transformer windings; CT; EMTP-ATP; delta side windings; differential equation; fault currents; internal inter-turn faults; power transformer protection; transformer equivalent circuit; transformer terminals; Circuit faults; Electrical fault detection; Equivalent circuits; Face detection; Fault detection; Magnetic flux; Oil insulation; Power transformers; Protective relaying; Surge protection; fault detection; internal faults; transformer protection; transient analysis;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
PowerTech, 2009 IEEE Bucharest
Conference_Location :
Bucharest
Print_ISBN :
978-1-4244-2234-0
Electronic_ISBN :
978-1-4244-2235-7
Type :
conf
DOI :
10.1109/PTC.2009.5282165
Filename :
5282165
Link To Document :
بازگشت