Lightning performance analysis of overhead subtransmission lines in power system
Author :
Phayomhom, A. ; Kulwongwit, W. ; Rugthaicharoencheep, N.
Author_Institution :
Dept. of Power Syst. Planning, Metropolitan Electr. Authority Bangkok, Bangkok, Thailand
fYear :
2014
fDate :
11-18 Oct. 2014
Firstpage :
2024
Lastpage :
2027
Abstract :
This paper analyzes the existing performance of insulator strings described in term of the total flash over rate (TFOR) for 69 kV and 115 kV subtransmission lines in a service area of Metropolitan Electricity Authority (MEA), Thailand. Presently, the design and installation of insulator strings for 69 kV and 115 kV subtransmission lines in MEA are based on American National Standards Institute (ANSI). The applications of this standard may not be appropriate for insulation coordination evaluation in MEA because of the different number of thunderstorm days. As a result, the failure on insulator strings of subtransmission system in MEA was often found. The results show that the difference in TFORs of the lines is significant for different thunderstorm days and probability peak current curves.
Keywords :
flashover; lightning protection; power overhead lines; power transmission protection; power transmission reliability; probability; thunderstorms; ANSI; American National Standards Institute; MEA; TFOR; Thailand; insulator string performance; lightning performance analysis; metropolitan electricity authority; overhead subtransmission line; power system; probability peak current curve; thunderstorm; total flash over rate; voltage 115 kV; voltage 69 kV; Estimation; Flashover; Lightning; Planning; Back flashover rate (BFOR); Insulator strings; Overhead ground wire (OHGW); Subtransmission lines;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Lightning Protection (ICLP), 2014 International Conference o
Conference_Location :
Shanghai
Type :
conf
DOI :
10.1109/ICLP.2014.6973462
Filename :
6973462
Link To Document :
بازگشت