  • Title

    A method to locate Partial Discharge Based on the theory of Sectional Winding Transfer Functions

  • Author

    Yini, Luo ; Lixing, Zhou

  • Author_Institution
    Changsha Univ. of Sci. & Technol., Changsha
  • fYear
    2007
  • Abstract
    In order to locate partial discharge (PD) source in transformer, ATP-Draw simulates the propagation of PD pulses along the windings model. Then the method of PD locating based on the theory of Sectional Winding Transfer Functions is introduced in detail, and simulation analysis and calculations indicate this method is effective and applicable. Moreover, some researches are explored based on the same theory to locate two or more PD sources by ANN. These researches can afford basic theories to PD online-monitoring and system diagnosis actually.
  • Keywords
    partial discharges; power engineering computing; transfer functions; transformer windings; ATP-Draw; PD online-monitoring; PD pulses propagation; partial discharge; sectional winding transfer functions; system diagnosis; transformer; windings model; Analytical models; Computational modeling; Mathematical model; Partial discharges; Power system modeling; Power transformer insulation; Power transformers; Pulse transformers; Transfer functions; Windings; ATP-Draw; PD location; transfer function; transformer windings model;