DocumentCode :
1730095
Title :
On-line partial discharge detection of MV cables with defect localisation (PDOL) based on two time synchronised sensors
Author :
van der Wielen, Peter C.J.M. ; Veen, Jeroen ; Wouters, Peter A.A.F. ; Steennis, E.Fred
Author_Institution :
Technische Universiteit Eindhoven - the Netherlands
fYear :
2005
Firstpage :
1
Lastpage :
5
Abstract :
A new and unique measuring system is presented for the online acquisition and analysis of partial discharges (PD-s) in medium-voltage power cables. The system is able to locate the origin(s) of PD-s by using two inductive sensors, each at one cable end. The measuring system is called PDOL, which stands for PD detection On-line with Localization. A patented solution is used for the time synchronization of the data intake at both cable ends and for the on-line calibration. One computer at a remote location collects data from various PDOL measuring systems for final presentation and interpretation. This paper discusses the basics of PDOL and some first measurement results.
fLanguage :
English
Publisher :
iet
Conference_Titel :
Electricity Distribution, 2005. CIRED 2005. 18th International Conference and Exhibition on
Conference_Location :