Title :
Un-powered thermal memory protection for circuit breakers
Author :
Lagree, James ; Walker, Christopher
Author_Institution :
Eaton Corp., Pittsburgh, PA, USA
Abstract :
The National Fire Protection Association (NFPA) 70, National Electrical Code contains extensive information and requirements for overcurrent protection and temperature limitations of conductors. Thermal-magnetic trip units in circuit breakers provide protection for overloads and short circuit faults in electrical distribution systems. The magnetic element protects against short circuit faults and a bimetal element protects against overloaded thermal conditions. Electronic trip units use microprocessors, electronic devices and software algorithms to provide the equivalent bi-metallic response of thermal-magnetic trip units. If the electronic trip unit does not contain unpowered thermal memory circuitry the protection is then not equivalent to the bimetal trip unit.
Keywords :
circuit breakers; fault diagnosis; overcurrent protection; power distribution; National Electrical Code; National Fire Protection Association 70; bimetal element; bimetallic response; circuit breakers; electrical distribution systems; electronic devices; electronic trip units; microprocessors; overcurrent protection; short circuit faults; software algorithms; temperature limitations; thermal-magnetic trip units; un-powered thermal memory protection; Circuit breakers; Circuit faults; Conductors; Cooling; Heating; Magnetic circuits; Microprocessors; Circuit Breakers; Overload Protection; Thermal memory;
Conference_Titel :
Pulp and Paper Industry Technical Conference (PPIC), Conference Record of 2010 Annual
Conference_Location :
San Antonio, TX
Print_ISBN :
978-1-4244-5676-5
DOI :
10.1109/PAPCON.2010.5556498