DocumentCode :
1735667
Title :
Combining Phasor Measurements to Monitor Cutset Angles
Author :
Dobson, Ian ; Parashar, Manu ; Carter, Chelsea
Author_Institution :
Univ. of Wisconsin, Madison, WI, USA
fYear :
2010
Firstpage :
1
Lastpage :
9
Abstract :
Power systems under stress can show large voltage angle differences between areas that can be monitored by wide area phasor measurements. One way to make this idea more specific is to choose a cutset of transmission lines that separates two power system areas and then define an angle difference across the cutset that is a suitable combination of the angle differences across lines of the cutset. We suggest that monitoring this cutset angle yields useful and specific information about power system stress.
Keywords :
phase measurement; power system measurement; power transmission lines; monitor cutset angles; power system stress; transmission lines; voltage angle differences; wide area phasor measurements; Area measurement; Goniometers; Load flow; Monitoring; Power measurement; Power system measurements; Power system modeling; Stress measurement; System testing; Transmission line measurements;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
System Sciences (HICSS), 2010 43rd Hawaii International Conference on
Conference_Location :
Honolulu, HI
ISSN :
1530-1605
Print_ISBN :
978-1-4244-5509-6
Electronic_ISBN :
1530-1605
Type :
conf
DOI :
10.1109/HICSS.2010.110
Filename :
5428359
Link To Document :
بازگشت