DocumentCode :
1740382
Title :
Long term monitoring of voltage sags at 6.6 kV distribution substation
Author :
Hiyama, Takashi ; Hirowatari, Takeshi
Author_Institution :
Dept. of Electr. & Comput. Eng., Kumamoto Univ., Japan
Volume :
2
fYear :
2000
fDate :
2000
Firstpage :
995
Abstract :
The paper presents the power quality monitoring results at a 6.6 kV distribution substation. The long term monitoring was performed during a year from October 1998 to November 1999 in order to evaluate the power quality of the 6.6 kV distribution system. Three-phase voltages and line currents were measured continuously at the site during the year. Whenever voltage sags were detected, the measured results were stored on the hard disk on a personal computer based data acquisition system. In this study, the harmonic distortions have also been investigated for the power quality evaluation and also for the identification of the causes of voltage sags. The effect of the load unbalance, i.e., one of the other factors of power quality, has also been investigated in this paper
Keywords :
computerised monitoring; data acquisition; distribution networks; harmonic distortion; power supply quality; power system harmonics; power system measurement; substations; 6.6 kV; data acquisition system; distribution substation; harmonic distortions; load unbalance; long term monitoring; power quality evaluation; power quality monitoring; three-phase line currents; three-phase voltages; voltage sags; Current measurement; Data acquisition; Distortion measurement; Hard disks; Microcomputers; Monitoring; Performance evaluation; Power quality; Substations; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power System Technology, 2000. Proceedings. PowerCon 2000. International Conference on
Conference_Location :
Perth, WA
Print_ISBN :
0-7803-6338-8
Type :
conf
DOI :
10.1109/ICPST.2000.897156
Filename :
897156
Link To Document :