            Abstract : 
A new valve regulated lead-acid (VRLA) gel motive power battery and PV system power center have been tested in the laboratory and at a PV hybrid telecommunication site. The power center provides battery charge control, system remote communications, and data acquisition at the field test site. Extensive laboratory and field-test data were used to improve battery performance by optimizing regulation voltages, finish-charge, and system design. After 1.5-years of service, battery and charge controller performance have met all performance requirements for the remote communications site at Sandia National Laboratories
         
        
            Keywords : 
battery storage plants; lead acid batteries; photovoltaic power systems; power system measurement; solar cell arrays; telecommunication power supplies; 1.5 y; PV hybrid VRLA battery test results; PV power system; battery charge control; battery performance; battery storage; data acquisition; finish-charge; regulation voltages; telecommunications site; valve regulated lead-acid gel motive power battery; Batteries; Communication system control; Control systems; Data acquisition; Design optimization; Laboratories; System testing; Telecommunication control; Valves; Voltage;
         
        
        
        