    This paper describes the development and testing of a software based flickermeter used in order to assess the supply quality from the LIMPET wave-power station on Islay. It describes the phenomenon of voltage flicker and the effect that a wave-power station has on this quantity. The paper also explains techniques developed in order to improve flickermeter performance when used with pre-recorded data. It also shows that the standard flickermeter sample frequency may be reduced for wave-station applications. Finally the paper presents flicker results from preliminary data collected from the LIMPET station and shows that the device is operating well within acceptable limits
  • Keywords
    computerised instrumentation; power engineering computing; power supply quality; voltage measurement; wave power plants; Islay; LIMPET wave-power station; flickermeter performance; oscillating water column; power quality assessment; pre-recorded data; software based flickermeter; supply quality assessment; testing; voltage flicker; wave-power station;