Study on the Operation Area of the 100Hz Protection in an HVDC System
Author
Li Zhikeng ; Chen Zhigang ; Wang Gang ; Li Haifeng
Author_Institution
Guangdong Electr. Power Design Inst., Guangzhou, China
fYear
2011
fDate
25-28 March 2011
Firstpage
1
Lastpage
4
Abstract
The 100 Hz protection function in an HVDC system is a backup protection for the ac system. The misoperation of the 100 Hz protection has severe effect on the safe and stable operation of the power system. Based on the proposed sequence switching-function model of the HVDC converter, and combined with the short circuit calculation program for the ac system, a practical method of calculation and Identification the operation area in the ac system for the 100 Hz protection is present in this paper. The asymmetric switching characteristic of the converter, involving the switching instant deviation and unbalanced commutation overlaps, and effects of the ac background harmonic to the dc side harmonic are considered in this method. The method is verified to be accurate and have great engineering practicability by simulation using the PSCAD/EMTDC software and the 500 kV ac power grid in the year 2008.
Keywords
HVDC power convertors; HVDC power transmission; power grids; power transmission protection; HVDC converter; HVDC system; PSCAD-EMTDC software; ac background harmonic; ac power grid; ac system; asymmetric switching characteristic; backup protection; dc side harmonic; frequency 100 Hz; power system; sequence switching-function model; short circuit calculation program; switching instant deviation; unbalanced commutation overlaps; voltage 500 kV; Circuit faults; Converters; HVDC transmission; Harmonic analysis; Integrated circuit modeling; Manganese; Switches;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Engineering Conference (APPEEC), 2011 Asia-Pacific
Conference_Location
Wuhan
ISSN
2157-4839
Print_ISBN
978-1-4244-6253-7
Type
conf
DOI
10.1109/APPEEC.2011.5748537
Filename
5748537
Link To Document