Synchrophasor-Assisted Zone 3 Operation
Author
Kundu, Pratim ; Pradhan, A.K.
Author_Institution
Dept. of Electr. Eng., Indian Inst. of Technol., Kharagpur, Kharagpur, India
Volume
29
Issue
2
fYear
2014
fDate
41730
Firstpage
660
Lastpage
667
Abstract
Zone 3 operation of distance relay serves as a remote backup in case of primary failure. Conditions, such as power swing, load encroachment, and voltage and transient instability, cause incorrect zone 3 operation. The detection of faults during such stressed conditions poses a further problem. This paper proposes a synchrophasor data-based technique for correct zone 3 operations by discriminating the fault from different stressed situations. This discrimination is accomplished using impedances calculated from voltage and current signals from synchrophasors placed at strategic locations. The proposed method is tested in the IEEE 39-bus New England system and found to be accurate.
Keywords
IEEE standards; fault currents; phasor measurement; relays; IEEE 39-bus New England system; current signals; distance relay; load encroachment; power swing; primary failure; remote backup; synchrophasor data-based technique; synchrophasor-assisted zone 3 operation; transient instability; voltage instability; voltage signals; zone 3 operation; Current measurement; Impedance; Impedance measurement; Indexes; Relays; Trajectory; Transmission line measurements; Discrete Fourier transform (DFT); distance relays; synchrophasor; zone 3 operation;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2013.2276071
Filename
6584021
Link To Document