• DocumentCode
    1757092
  • Title

    Synchrophasor-Assisted Zone 3 Operation

  • Author

    Kundu, Pratim ; Pradhan, A.K.

  • Author_Institution
    Dept. of Electr. Eng., Indian Inst. of Technol., Kharagpur, Kharagpur, India
  • Volume
    29
  • Issue
    2
  • fYear
    2014
  • fDate
    41730
  • Firstpage
    660
  • Lastpage
    667
  • Abstract
    Zone 3 operation of distance relay serves as a remote backup in case of primary failure. Conditions, such as power swing, load encroachment, and voltage and transient instability, cause incorrect zone 3 operation. The detection of faults during such stressed conditions poses a further problem. This paper proposes a synchrophasor data-based technique for correct zone 3 operations by discriminating the fault from different stressed situations. This discrimination is accomplished using impedances calculated from voltage and current signals from synchrophasors placed at strategic locations. The proposed method is tested in the IEEE 39-bus New England system and found to be accurate.
  • Keywords
    IEEE standards; fault currents; phasor measurement; relays; IEEE 39-bus New England system; current signals; distance relay; load encroachment; power swing; primary failure; remote backup; synchrophasor data-based technique; synchrophasor-assisted zone 3 operation; transient instability; voltage instability; voltage signals; zone 3 operation; Current measurement; Impedance; Impedance measurement; Indexes; Relays; Trajectory; Transmission line measurements; Discrete Fourier transform (DFT); distance relays; synchrophasor; zone 3 operation;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2013.2276071
  • Filename
    6584021