• DocumentCode
    1757729
  • Title

    Reduction of Stray Losses in Flange–Bolt Regions of Large Power Transformer Tanks

  • Author

    Olivares-Galvan, J.C. ; Magdaleno-Adame, S. ; Escarela-Perez, R. ; Ocon-Valdez, Rodrigo ; Georgilakis, P.S. ; Loizos, George

  • Author_Institution
    Dept. de Energia, Univ. Autonoma Metropolitana de Azcapotzalco, Mexico City, Mexico
  • Volume
    61
  • Issue
    8
  • fYear
    2014
  • fDate
    Aug. 2014
  • Firstpage
    4455
  • Lastpage
    4463
  • Abstract
    In large power transformers, the presence of stray currents in the structural elements near the high current bushings can be considerable, and this leads to hot spots. This work presents a practical analysis of overheating in the bolts that join the tank and the cover, which are near the high current bushings of the transformer. Overheating results are analyzed and discussed for the case of a 420-MVA transformer. The hot spots in the flange-bolt regions are discovered by thermal maps that are obtained during power transformer operation as a part of a preventive maintenance program. In this paper, we use copper links to ensure the connection of both the cover and tank body, significantly reducing the overheating of the flange-bolt region. The copper link solution has been validated by measurements. We have used calibrated measurement instruments in all the experiments. Moreover, a 3-D finite-element analysis of the geometry of interest has been used to verify the copper link solution.
  • Keywords
    bushings; calibration; fasteners; finite element analysis; flanges; losses; power transformer insulation; preventive maintenance; tanks (containers); 3D finite element analysis; apparent power 420 MVA; copper link; flange-bolt region; high current bushings; measurement instruments calibration; overheating reduction; power transformers tank; preventive maintenance program; stray current; stray loss reduction; structural elements; tank cover; thermal maps; Copper; Fasteners; Finite element analysis; Heating; Oil insulation; Power transformer insulation; Flange–bolt regions; hot spots; low-voltage (LV) bushings; overheating; power transformer; stray currents; tank cover; thermography; transformer failures;
  • fLanguage
    English
  • Journal_Title
    Industrial Electronics, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0278-0046
  • Type

    jour

  • DOI
    10.1109/TIE.2013.2279373
  • Filename
    6584734