Title :
A New Hybrid Power Conditioner for Suppressing Harmonics and Neutral-Line Current in Three-Phase Four-Wire Distribution Power Systems
Author :
Jinn-Chang Wu ; Hurng-Liahng Jou ; Hsin-Hsing Hsaio ; Shun-Tian Xiao
Author_Institution :
Dept. of Microelectron. Eng., Nat. Kaohsiung Marine Univ., Kaohsiung, Taiwan
Abstract :
In this paper, a new hybrid power conditioner is proposed for suppressing harmonic currents and neutral-line current in three-phase four-wire distribution power systems. The proposed hybrid power conditioner is composed of a neutral-line current attenuator and a hybrid power filter. The hybrid power filter, configured by a three-phase power converter and a three-phase tuned power filter, is utilized to filter the nonzero-sequence harmonic currents in the three-phase four-wire distribution power system. The three-phase power converter is connected to the inductors of the three-phase tuned power filter in parallel, and its power rating can thus be reduced effectively. The tuned frequency of the three-phase tuned power filter is set at the fifth harmonic frequency. The neutral-line current suppressor is connected between the power capacitors of the three-phase tuned power filter and the neutral line to suppress the neutral-line current in the three-phase four-wire distribution power system. With the major fundamental voltage of the utility dropping across the power capacitors of the three-phase tuned power filter, the power rating of the neutral-line current suppressor can thus be reduced. Hence, the proposed hybrid power conditioner can effectively reduce the power rating of passive and active elements. A hardware prototype is developed to verify the performance of the proposed hybrid power conditioner. Experimental results show that the proposed hybrid power conditioner achieves expected performance.
Keywords :
distribution networks; power convertors; power harmonic filters; fifth harmonic frequency; harmonic current suppression; hybrid power conditioner; hybrid power filter; neutral-line current attenuator; neutral-line current suppressor; three-phase four-wire distribution power systems; three-phase power converter; three-phase tuned power filter; Attenuators; Harmonic analysis; Hybrid power systems; Inductors; Power system harmonics; Pulse width modulation; Harmonic; neutral-line current; power converter;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.2014.2322615