• DocumentCode
    1765189
  • Title

    Frequency Response Analysis for Phase-Shifting Transformers in Oil Field Facilities

  • Author

    Xiaodong Liang ; El-Kadri, Ahmed ; Stevens, Jonathan ; Adedun, Rotimi

  • Author_Institution
    Sch. of Eng. & Comput. Sci., Washington State Univ. - Vancouver, Vancouver, WA, USA
  • Volume
    50
  • Issue
    4
  • fYear
    2014
  • fDate
    July-Aug. 2014
  • Firstpage
    2861
  • Lastpage
    2870
  • Abstract
    Phase-shifting transformers for variable frequency drives (VFDs) are usually specialty designed, and their applications become more common in oil field facilities. The frequency response analysis (FRA) method has been recognized as a useful maintenance tool for transformers; however, very limited work has been done on phase-shifting transformers for maintenance and troubleshooting using the FRA method. In this paper, the FRA baseline measurement is conducted on a healthy delta-polygon-polygon winding phase-shifting transformer for a 12-pulse VFD system in a laboratory. The test data are presented and analyzed, which could serve as the baseline reference and provide valuable information for the maintenance of phase-shifting transformers with similar design.
  • Keywords
    crude oil; electrical maintenance; power transformers; transformer windings; transformers; variable speed drives; electrical maintenance; frequency response analysis method; healthy delta-polygon-polygon winding; oil field facility; phase shifting transformer; transformer troubleshooting; variable frequency drive; Frequency measurement; Frequency response; Impedance; Impedance measurement; Oil insulation; Power transformers; Windings; Frequency response analysis (FRA); oil field facilities; phase shifting; phase-shifting; polygon winding; tap position; transformers;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.2013.2291936
  • Filename