DocumentCode
1773272
Title
Effect of voltage rise time on time-to-failure of form-wound stator coil enamelled turn insulation
Author
Moonesan, Mohammad Saleh ; Jayaram, Shesha ; Cherney, Ed ; Omranipour, Ramtin ; Ul Haq, Saeed
Author_Institution
Electr. & Comput. Eng. Dept., Univ. of Waterloo, Waterloo, ON, Canada
fYear
2014
fDate
8-11 June 2014
Firstpage
167
Lastpage
171
Abstract
The paper presents the results of aging of medium voltage stator coil enamelled turn insulation under square waves having rise times of 270 ns and 4.5 μs. Unipolar square waves having a peak voltage of 2.5 kV and a switching frequency of 3 kHz were applied to enamelled wire samples while measuring online partial discharge. A two-parameter Weibull distribution was employed for analysis of the effect of rise time on insulation life. The tests were repeated at 6 kV peak with duty cycles of 15% and 50% for both rise times. The analysis indicates that insulation life is dependent on voltage rise time only when the DC component of the wave is short.
Keywords
Weibull distribution; ageing; coils; enamels; insulating materials; partial discharge measurement; stators; DC component; aging; enamelled turn insulation; form-wound stator coil; frequency 3 kHz; insulation life; medium voltage stator coil; online partial discharge measurement; switching frequency; time 270 ns; time 4.5 mus; time-to-failure; two-parameter Weibull distribution; unipolar square waves; voltage rise time; Aging; Generators; Insulation; Partial discharges; Stress; Switching frequency; Voltage measurement; Aging; Form-Wound; Rise Time; Square wave; Time-to-Failure; Turn Insulation;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation Conference (EIC), 2014
Conference_Location
Philadelphia, PA
Print_ISBN
978-1-4799-2787-6
Type
conf
DOI
10.1109/EIC.2014.6869368
Filename
6869368