DocumentCode
1773278
Title
On-line partial discharge analysis of transmission and distribution assets
Author
Lewin, P.L.
Author_Institution
Tony Davies High Voltage Lab., Univ. of Southampton, Southampton, UK
fYear
2014
fDate
8-11 June 2014
Firstpage
180
Lastpage
184
Abstract
It is becoming increasingly clear that methodologies for PD classification based on standard laboratory experimental data are not readily applicable when assessing on-line PD data measured in the field. It is not just that field data is corrupted by noise and disturbance, but also the significant differences between typical laboratory experiments to generate PD data and the generation of PDs in high voltage plant due to degradation of the insulation system. In this paper, the use of nonlinear time-series analysis on field data is shown to yield useful information, methods involving dimension reduction techniques are shown to allow identification of different sources and finally a method for designing standard finite impulse response filters that approximate the nonlinear analytical approach and are easy to implement in condition monitoring systems are discussed.
Keywords
FIR filters; condition monitoring; partial discharge measurement; stochastic processes; time series; finite impulse response filters; insulation system; nonlinear time series analysis; online partial discharge analysis; Frequency measurement; Insulation; Laboratories; Partial discharges; Pulse measurements; Time series analysis; Windings; clustering; condition monitoring; partial discharge; stochastic analysis; time series analysis;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation Conference (EIC), 2014
Conference_Location
Philadelphia, PA
Print_ISBN
978-1-4799-2787-6
Type
conf
DOI
10.1109/EIC.2014.6869371