DocumentCode :
1774282
Title :
Transient fault location for HVDC transmission lines based on voltage distribution and one-terminal information
Author :
Li Bao-de ; Tan Jian-cheng
Author_Institution :
Smart Substation Technol. & Applic. Lab., Guangxi Univ., Nanning, China
fYear :
2014
fDate :
23-26 Sept. 2014
Firstpage :
508
Lastpage :
510
Abstract :
A transient fault location method based on voltage distribution over the HVDC line is proposed in the paper. The proposed algorithm calculates the voltage derivatives along the line using the distributed parameter model of high voltage direct current (HVDC) transmission line, and uses this information to obtain the boundary point between steady state and transient state line sections after a fault, then derived the fault distance from the measuring point. Extensive PSCAD/ EMTDC simulation studies show that the proposed algorithm is feasible, accurate, not affected by fault resistance, with calculation error is within two hundred meters.
Keywords :
HVDC power transmission; fault location; power distribution faults; power distribution lines; power system measurement; power system transients; power transmission faults; power transmission lines; HVDC transmission line; PSCAD-EMTDC simulation; distributed parameter model; fault resistance; high voltage direct current transmission line; one-terminal information; steady state line section; transient fault location method; transient state line section; voltage distribution; Abstracts; HVDC transmission; Resistors; HVDC; distributed parameter model; fault location; simulation; transient;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electricity Distribution (CICED), 2014 China International Conference on
Conference_Location :
Shenzhen
Type :
conf
DOI :
10.1109/CICED.2014.6991760