This paper examines the fault ride-through strategy of a three-phase PV system with respect to compliance to the German Transmission Code. Specifically, the paper examines the case of a single line-ground fault which occurs predominantly in the distribution system. The paper proposes the injection of reactive power on a per-phase basis to the faulty phases while maintaining active power injection to the healthy phases thereby avoiding power generation deficit. Simulation results from a study performed in MATLAB/Simulink with the SimPowerSystem toolbox present the unbalanced nature of currents during an unbalanced fault. An experimental setup has been shown and described that has been used to implement the strategy. Experimental results have been provided to validate the simulation results.
Keywords
DC-AC power convertors; photovoltaic power systems; reactive power; active power injection; asymmetrical fault ride through; four wire DC AC converters; reactive power; single line ground fault; three phase PV systems; Carbon dioxide; Companies; Integrated circuit modeling; Power demand; Simulation; Topology; Wires; Grid compliance; current control; four-wire dc-ac converter; phase locked loop;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics Conference (IPEC-Hiroshima 2014 - ECCE-ASIA), 2014 International
Conference_Location
Hiroshima
Type
conf
DOI
10.1109/IPEC.2014.6869996
Filename
6869996
Link To Document