Title :
An accident analysis of a smart substation
Author :
XueYuan Niu ; JianFan Zhai ; Chunlin Li ; Chao Li ; JuYuan Niu
Author_Institution :
State Grid Henan Electr. Power Co. Maintenance Co., Zhengzhou, China
Abstract :
This article records and analyses an accident happened in a 500kV smart substation, which was caused by a single-phase ground fault happened to a 500kV transmission line in the power grid. The accident provoked false action of the differential protection of main transformer, false action of the differential protection of 220kV bus and false action of line differential protection of several 220kV transmission lines. The accident caused the power losing of transformer, several 220kV transmission lines and 220kV north bus. Through the analysis of the fault wave of the tripping devices, we know that these false actions of differential protections were caused by the un- synchronism of sampled data of current of 220kV equipments supplied by merging units. This accident show the importance of the synchronism of sample data, so it´s an essential step to examine synchronism of the MUs in the smart substation before it puts into operation.
Keywords :
electrical accidents; power transformer protection; power transmission faults; power transmission lines; smart power grids; substation protection; synchronisation; MU synchronism; accident analysis; false action protection; north bus protection; power grid; power losing; sampled data unsynchronism; single-phase ground fault wave; smart substation; transformer protection; transmission line; tripping devices; voltage 220 kV; voltage 500 kV; Abstracts; Current measurement; Delays; Electricity; Optical fiber devices; Substations; False Action; Merging Unit; Sampled Data; Smart Substation; Synchronism;
Conference_Titel :
Electricity Distribution (CICED), 2014 China International Conference on
Conference_Location :
Shenzhen
DOI :
10.1109/CICED.2014.6991853