• DocumentCode
    1774496
  • Title

    The analysis of the integral cycle delay of the electronic transformer and the research on the detection technology

  • Author

    Jian Zhang ; Meimei Duan ; Xiaoxing Mu

  • Author_Institution
    State Grid Jiangsu Electr. Power Res. Inst., Nanjing, China
  • fYear
    2014
  • fDate
    23-26 Sept. 2014
  • Firstpage
    1037
  • Lastpage
    1040
  • Abstract
    In the application of the electronic transformer, one often observes the phenomenon of whole cycle delay. During the process of electronic transformer´s converting analog signals into digital signals, the data process units play a key role. If there is a delay of these units sending the data, the whole cycle delay will follow. In this paper, the reason for the whole cycle delay of electronic transformer is analysed. The detection principle and method for such phenomenon are proposed. Based on the concept of power source triggered by a pulse and the first-frequency-output power source, testing equipments are designed and introduced.
  • Keywords
    power transformers; test equipment; analog signals; data process units; detection technology; digital signals; electronic transformer; integral cycle delay; power source; testing equipments; Abstracts; Delays; Merging; Substations; electronic transformer; integral cycle delay; merging unit;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electricity Distribution (CICED), 2014 China International Conference on
  • Conference_Location
    Shenzhen
  • Type

    conf

  • DOI
    10.1109/CICED.2014.6991863
  • Filename