DocumentCode
1774516
Title
Modeling and performance assessment of PV plants based on field-test of power generation unit
Author
Jingsheng Huang ; Junjun Zhang ; Hongtao Li ; Meiyin Liu ; Wei Dong
Author_Institution
China Electr. Power Res. Inst., Nanjing, China
fYear
2014
fDate
23-26 Sept. 2014
Firstpage
1085
Lastpage
1088
Abstract
PV power plants should meet technical requirements before connected to grid. Due to the equipment capacity and cost constraints, low voltage ride through (LVRT) of the plants can not be directly tested. In this paper, the methods to assess PV plants performance based on the field test of power generation unit (PGU) are introduced. At first, the way to test LVRT capability of PGU is put forwarded, and then modeling and model correction is developed with t DIgSILENT Power- Factory. After the correction of PGU model, the whole PV plants model is built, including a mount of inverters, transformers, PV arrays, cabbles and other key components. The LVRT performance of PV plants is evaluated by the simulation result.
Keywords
invertors; photovoltaic power systems; power engineering computing; power grids; power system simulation; solar cell arrays; transformers; DIgSILENT power-factory; LVRT capability; PGU; PV arrays; PV plant model; PV power plants; inverters; low voltage ride through; photovoltaic power plants; power generation unit; transformers; Abstracts; Analytical models; Automation; Data models; Electricity; Joining processes; Standards; DIgSILENT PowerFactory; LVRT; PV plants; field testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Electricity Distribution (CICED), 2014 China International Conference on
Conference_Location
Shenzhen
Type
conf
DOI
10.1109/CICED.2014.6991872
Filename
6991872
Link To Document