  • Title

    Condition assessment of main insulation in transformer by dielectric loss data interpolation method and database building

  • Author

    Jian Hao ; Jin Fu ; Zhiqin Ma ; Shihai Zhang ; Shan Shen

  • Author_Institution
    State Grid Chongqing Electr. Power Co. Chongqing Electr. Power Res. Inst., Chongqing, China
  • fYear
    2014
  • fDate
    1-5 June 2014
  • Firstpage
    152
  • Lastpage
    155
  • Abstract
    Frequency Domain Spectroscopy (FDS) diagnostic technique is becoming more popular in recent years and is more suitable for onsite assessment. However, there are few reports about how to use FDS to assess the ageing condition of the oil-paper insulation conveniently. What´s more, the lower frequency testing would be taken three or more hours. It´s useful to reduce the testing time without effect the assessment result using new data processing method. In this paper, the oil impregnated insulation pressboard samples were thermally aged at 130°C for different times and then they were prepared for different moisture contents. The FDS measurements were taken on them and the dielectric loss of all the samples were calculated by dielectric loss interpolation. The ageing condition assessment database which contains five ageing levels and five moisture contents was built. When the dielectric loss interpolation curves of the oil impregnated insulation pressboard in a transformer mostly coincide with one curve or locate between two curves in the database, the main insulation ageing condition of the transformer is known. The evaluation method proposed is verified in this paper and the result shows that the dielectric loss interpolation method is dependable.
  • Keywords
    ageing; dielectric losses; impregnated insulation; interpolation; power transformer insulation; FDS diagnostic technique; FDS measurements; ageing condition assessment database; data processing method; database building; dielectric loss data interpolation curves; frequency domain spectroscopy diagnostic technique; loss; lower frequency testing; main insulation condition assessment; moisture contents; oil impregnated insulation pressboard samples; oil-paper insulation; onsite assessment; temperature 130 degC; testing time reduction; thermally aged; transformer; Moisture measurement; Voltage measurement; Windings; condition assessment; dielectric loss; frequency domain spectroscopy; insulation; transformer;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulating Materials (ISEIM), Proceedings of 2014 International Symposium on
  • Conference_Location
    Niigata
  • Type

    conf

  • DOI
    10.1109/ISEIM.2014.6870743
  • Filename
    6870743