• DocumentCode
    1775129
  • Title

    Assessment of 300MW turbine generator stator insulation

  • Author

    Lijun Wang ; Yizhong Zhang ; Wenjing Jin ; Jingzhe Shi ; Song Zhou ; Qiang Li ; Song Liu

  • Author_Institution
    Generator Plant, Shanghai Electr. Power Generation Equip. Co., Ltd., Shanghai, China
  • fYear
    2014
  • fDate
    1-5 June 2014
  • Firstpage
    500
  • Lastpage
    502
  • Abstract
    The 300MW turbine generator which uses Tung oil-BMI-epoxy resin-rich insulation in Wu Jing Thermal Power Plant was subjected to a wide variety of diagnostic tests during the regular planned overhaul. This generator has kept safely running for 23 years since 1991. Diagnostic tests included direct current diagnostic tests, capacitance, dissipation factor and tip-up, partial discharge, AC proof voltage test. Meanwhile, a new generator (reference generator) with the same structure was tested. The aging degradation of generator stator insulation is assessed by comparison the data of diagnostic tests for two generators. It is concluded that the aging situation of the candidate generator stator insulation is not serious and still meets the requirements of operation after safely running 23 years.
  • Keywords
    epoxy insulation; machine insulation; machine testing; stators; turbogenerators; AC proof voltage test; Tung oil-BMI-epoxy resin-rich insulation; Wu Jing Thermal Power Plant; aging degradation; direct current diagnostic tests; dissipation factor; partial discharge; power 300 MW; reference generator; regular planned overhaul; time 23 yr; tip-up; turbine generator stator insulation; Insulation; Manganese; Tung oil-BMI-epoxy resin-rich insulation system; diagnostic test; stator insulation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulating Materials (ISEIM), Proceedings of 2014 International Symposium on
  • Conference_Location
    Niigata
  • Type

    conf

  • DOI
    10.1109/ISEIM.2014.6870828
  • Filename
    6870828