DocumentCode :
1776608
Title :
Influence of grid-connected inverters on the power quality of the distribution grid
Author :
Verhelst, Bart ; Van Ryckeghem, Jurgen ; Desmet, Jan
Author_Institution :
Res. group Lemcko, Ghent Univ. campus Kortrijk, Kortrijk, Belgium
fYear :
2014
fDate :
18-20 June 2014
Firstpage :
670
Lastpage :
675
Abstract :
Many inverters are quoted as having a PF of better than 0.95 when in reality, the true power factor is between 0.5 and 0.75. This paper describes the influence of grid-connected inverters on the distribution grid. The impact of the voltage distortion from the inverter to the distribution grid is relative small without grid impedance. When the grid impedance is involved, the distortion will become higher and so, more harmonics will be injected into the grid. The impact of the current distortion is especially high at low power output, but decreases fast at moderate or high power. If the background distortion of the grid increases, there will be an increase of the voltage and current harmonics. The specific limits of the EN 50160 and IEC 61000-3-12 could be exceeded at such high pollution.
Keywords :
harmonic distortion; invertors; power grids; power supply quality; power system harmonics; EN 50160; IEC 61000-3-12; background distortion; current distortion; current harmonics; distribution grid; grid impedance; grid-connected inverters; true power factor; voltage distortion; voltage harmonics; Harmonic analysis; Harmonic distortion; Impedance; Inverters; Phase distortion; Power system harmonics; Renewable energy; inverter; normalisation; power quality;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Electronics, Electrical Drives, Automation and Motion (SPEEDAM), 2014 International Symposium on
Conference_Location :
Ischia
Type :
conf
DOI :
10.1109/SPEEDAM.2014.6872002
Filename :
6872002