DocumentCode
1777302
Title
Analysis of harmonic resonances among parallel grid-connected inverters
Author
Sun Zhen-Ao ; Yang Zi-long ; Wang Yi-bo ; Xu Hong-hua
Author_Institution
Inst. of Electr. Eng., Beijing, China
fYear
2014
fDate
20-22 Oct. 2014
Firstpage
3071
Lastpage
3077
Abstract
The resonances in parallel grid-connected PV inverters were studied. Considering the effect from the step-up transformers and grid impedance, the transfer functions of different inputs to the output were derived; furthermore, the deficiencies of conventional inverters were pointed out, and a novel method was proposed, which can effectively suppress the harmonic current output, thus avoiding the resonance phenomenon, without any changes of the topology. Then compared Block Diagrams before and after applying the proposed method, theoretically proved the correctness of the virtual conductance method; Finally, simulation models were built to restore resonance phenomenon and to verify the feasibility of the method.
Keywords
harmonic analysis; harmonics suppression; invertors; photovoltaic power systems; resonance; transfer functions; transformers; block diagram; grid impedance; harmonic current suppression; harmonic resonances analysis; parallel grid-connected PV inverter; photovoltaic inverter; resonance phenomenon; step-up transformer; transfer function; virtual conductance method; Active filters; Harmonic analysis; Impedance; Inverters; Power harmonic filters; Resonant frequency; grid-connected inverters; resonances; transfer function; virtual conductance;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology (POWERCON), 2014 International Conference on
Conference_Location
Chengdu
Type
conf
DOI
10.1109/POWERCON.2014.6993560