DocumentCode :
1777735
Title :
Study on transients and effect on capacitor voltage transformer caused by disconnector switching of UHV Series Capacitor Banks
Author :
Han Bin ; Xiang Zutao ; Ban Liangeng ; Ma Qiyan ; Liu Weidong
Author_Institution :
China Electr. Power Res. Inst., Beijing, China
fYear :
2014
fDate :
20-22 Oct. 2014
Firstpage :
2293
Lastpage :
2298
Abstract :
During the system commissioning test of Ultra High Voltage (UHV) project with Series Capacitors Banks (SCB), the adjacent capacitor voltage transformer (CVT) was damaged during the switching operation of disconnectors of SCB. In this paper, the transients on adjacent CVT caused by disconnector switching of UHV SCB were studied by simulation. The causes of damage of CVT were analyzed. The effectiveness of suppressing the transients by use of damping resistor of disconnector, series reactor and series resistor were studied by simulation. In UHV AC test base, a test circuit was established. It includes true type UHV SCB platform, UHV CVT and disconnector. Tests were carried out when the circuit was with or without limitation measures. Test results were compared with the simulation results. The simulation and Test results were in agreement.
Keywords :
damping; potential transformers; power transformer testing; transients; CVT; UHV AC test; UHV SCB; UHV series capacitor banks; capacitor voltage transformer; damping resistor; disconnector switching; series reactor; series resistor; ultra high voltage project; Current measurement; Damping; Inductors; Resistors; Switches; Transient analysis; capacitor voltage transformer; disconnector; fast transient; series capacitor banks; ultra high voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power System Technology (POWERCON), 2014 International Conference on
Conference_Location :
Chengdu
Type :
conf
DOI :
10.1109/POWERCON.2014.6993808
Filename :
6993808
Link To Document :
بازگشت