A generator control strategy for reducing the load shedding amount after the UHVDC commutation failure
Author
Yi Xiaoyu ; Wang Yuanyuan ; Guo Weimin ; Wei Qiang ; Tang Yaohua
Author_Institution
North China Electr. Power Univ., Baoding, China
fYear
2014
fDate
20-22 Oct. 2014
Firstpage
1001
Lastpage
1007
Abstract
In the power grid of "strong DC and weak AC", the commutation failure of the ultra-high voltage (UHV) line will result in angle swing between two regional power grids. Our analysis show that, unlike the scenario in the single machine infinite bus system, the speed of angle swing between two regional power grids after the fault is slow since power vacant is not very large (compared with the moment of inertia of the regional power grid). The first swing may last for several seconds. In this paper it is possible to improve the stability by changing generators output. We propose a new control strategy in this paper. The control strategy is as follows: when UHV commutation failure happens, signals are sent to generators in local power grid so that they can increase power output to compensate for the power vacant. At the same time, signals are also sent to generators in remote regional power grid to decrease their power output. This way, out of step can be avoided. Under typical simulation parameters configuration, a generator can increase/decrease mechanical power output by 6 % in 4s after the fault happens. The simulation results show that this strategy can decrease the amount of load shedding from 10.3 % to 6 % after commutation failure happens in UHV DC line connected to Henan province.
Keywords
HVDC power transmission; commutation; electric generators; failure analysis; load shedding; machine control; power grids; power system transient stability; power transmission control; power transmission faults; power transmission lines; power transmission reliability; UHV line; UHVDC commutation failure; angle swing; generator control strategy; load shedding reduction; local power grid; mechanical power output; power vacant; regional power grids; simulation parameter configuration; single machine infinite bus system; transient stability; ultra-high voltage; Frequency control; Generators; Load modeling; Power grids; Power system stability; Stability analysis; Valves; direct current (DC) latching; load shedding; transient stability; ultra-high voltage (UHV);
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology (POWERCON), 2014 International Conference on
Conference_Location
Chengdu
Type
conf
DOI
10.1109/POWERCON.2014.6993937
Filename
6993937
Link To Document