Title
Influence of AC voltage prestressing on AC electrical-tree inception of deteriorated LDPE with dried water-tree
Author
Asai, D. ; Kurimoto, M. ; Komori, F. ; Kato, Toshihiko ; Funabashi, Toshihisa ; Suzuoki, Y.
Author_Institution
Nagoya Univ., Nagoya, Japan
fYear
2014
fDate
19-22 Oct. 2014
Firstpage
385
Lastpage
388
Abstract
In order to improve the accuracy of degradation diagnosis for CV power cables, it is important to clarify the inception and propagation mechanisms of electrical tree degradation from water tree degradation. This paper presents the influence of AC voltage prestressing on the inception voltage of AC electrical-tree in the deteriorated LDPE with dried water-tree. The experiment was carried out with a small LDPE-block (3 mm×10 mm×15 mm) with the needle-plane electrode system, in which the inception voltage of AC electrical-tree of LDPE without water tree was from 5 kVrms to 8kVrms. The prestressing conditions, i.e. the ambient temperature, the voltage amplitude and the voltage duration time, were varied. The results suggest that the degradation under AC voltage application is enhanced by the existence of water-tree degradation and affects AC electrical-tree inception.
Keywords
polyethylene insulation; power cable testing; trees (electrical); AC electrical-tree inception; AC voltage application; AC voltage prestressing; CV power cables; LDPE-block; ambient temperature; degradation diagnosis; deteriorated LDPE; dried water-tree; electrical tree degradation; inception voltage; needle-plane electrode system; prestressing conditions; propagation mechanisms; voltage amplitude; voltage duration time; water tree degradation; Degradation; Electrodes; Needles; Optical filters; Partial discharges; Trees - insulation; Voltage measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena (CEIDP), 2014 IEEE Conference on
Conference_Location
Des Moines, IA
Type
conf
DOI
10.1109/CEIDP.2014.6995749
Filename
6995749