Abstract :
The paper investigates effects of Kraft Paper to prevent bridging in pressboard fibre contaminated transformer oil. There are three different configuration of Kraft paper tested. These are 1) covered electrode with loose bond, 2) tight bond and 3) bare electrode with a paper barrier in the middle. There were no bridges formed with loosely bonded tests with DC electric fields. For the other two cases, there was always a complete bridge formed.
Keywords :
contamination; paper; power transformer insulation; transformer oil; bare electrode; covered electrode; kraft paper barriers; paper barrier; pressboard fibre contaminated transformer oil; Bridge circuits; Electric fields; Electrodes; Oil insulation; Optical fibers; Power transformer insulation; Coulomb force; bridging; charge transportation; dielectrophoresis; transformer oil;