Title :
Grounding Grid Corrosion Diagnosis Based on Large Change Sensitivity
Author :
Liu, Liqiang ; Luo, Xianjue ; Niu, Tao ; Wang, Kai
Author_Institution :
Sch. of Electr. Eng., Xi´´an Jiaotong Univ., Xi´´an, China
Abstract :
The method of corrosion diagnosis for substation grounding grids based on large change sensitivity is proposed. By analyzing the node voltages, the large change sensitivity of the port voltages in response to the branch resistances is given and the nonlinear optimal model of corrosion diagnosis is established. The diagnosis equations based on the differential sensitivity were set up in traditional methods. Contrasting with them, the equations established in the paper is more appropriate for the real corrosion case. To insure the independency of diagnosis equations, the optimal selection method of test ports is put up. The effectiveness of algorithm is validated by the simulation of substation grounding grids.
Keywords :
corrosion protection; corrosion resistance; earthing; power grids; branch resistance; change sensitivity; corrosion diagnosis equation; differential sensitivity; grid corrosion diagnosis; nonlinear optimal model; optimal selection; substation grounding grid; Accidents; Circuits; Conductors; Corrosion; Differential equations; Electromagnetic measurements; Grounding; Nonlinear equations; Substations; Voltage; corrosion diagnosis; grounding grid; large change sensitivity; nonlinear optimal model;
Conference_Titel :
Information Assurance and Security, 2009. IAS '09. Fifth International Conference on
Conference_Location :
Xian
Print_ISBN :
978-0-7695-3744-3
DOI :
10.1109/IAS.2009.241