  • Title

    Electroluminescence for XLPE cable diagnosis

  • Author

    Ishii, R. ; Iemura, S. ; Kubo, M. ; Nagura, N. ; Shimizu, N.

  • Author_Institution
    Kansai Electr. Power Co., Inc., Hyogo, Japan
  • Volume
    1
  • fYear
    2003
  • fDate
    1-5 June 2003
  • Firstpage
    199
  • Abstract
    Electrical treeing is responsible for the breakdown of power cables with polymeric insulation, such as low density polyethylene (LDPE) and cross-linked polyethylene (XLPE). Electroluminescence (EL) occurs in the initiation phase of electrical tree. We studied the characteristics of EL in XLPE cut from 77 kV class power cables. We found that EL intensity in XLPE cut from removed cable gradually decreases with voltage application time compared with that in unaged XLPE. This tendency is considered to reflect the degradation in XLPE.
  • Keywords
    XLPE insulation; electric breakdown; electroluminescence; organic insulating materials; power cable insulation; trees (electrical); LDPE; XLPE cable diagnosis; XLPE degradation; breakdown; cross-linked polyethylene; electrical tree; electroluminescence; low density polyethylene; polymeric insulation; Cable insulation; Dielectrics and electrical insulation; Electric breakdown; Electroluminescence; Plastic insulation; Polyethylene; Polymers; Power cables; Trees - insulation; Voltage;