• DocumentCode
    1820844
  • Title

    Robust evaluation procedure for lightning impulses

  • Author

    Hackemack, K. ; Gockenbach, E.

  • Author_Institution
    Inst. of Electr. Power Syst., Hannover Univ., Germany
  • Volume
    2
  • fYear
    2003
  • fDate
    1-5 June 2003
  • Firstpage
    518
  • Abstract
    The existing recommendation for high voltage tests, IEC Publication 60060, is ambiguous in the evaluation of the impulse test voltage, when oscillations or overshoot are superimposed on the peak of the smooth, double exponential waveshape. Particularly impulse tests on transformers may be critical due to the high stress on the insulation during the impulse tests. The contribution describes a proposal for the evaluation with a frequency dependent test voltage factor which is derived from experimental investigations with some basic insulation materials. The test voltage factor method allows robust evaluation procedures which can be used for manual as well as for automatic evaluation. Presenting some examples the contribution shows that the proposed methods are suitable to increase the reproducibility and reliability of lightning impulse tests.
  • Keywords
    impulse testing; potential transformers; reliability; double exponential waveshape; frequency dependent impulse test voltage factor; high voltage tests; lightning impulse test; reliability; robust evaluation; transformers; Frequency dependence; IEC standards; Impulse testing; Insulation testing; Lightning; Materials testing; Power transformer insulation; Proposals; Robustness; Stress;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Properties and Applications of Dielectric Materials, 2003. Proceedings of the 7th International Conference on
  • ISSN
    1081-7735
  • Print_ISBN
    0-7803-7725-7
  • Type

    conf

  • DOI
    10.1109/ICPADM.2003.1218467
  • Filename
    1218467