Title :
Improving UHF partial discharge location in high voltage equipment
Author :
Pinpart, Tanya ; Judd, Martin D.
Author_Institution :
Dept. of Electron. & Electr. Eng., Univ. of Strathclyde, Glasgow, UK
Abstract :
Insulation degradation in high voltage equipment may be caused by partial discharge activity. In this paper we investigate possible techniques for improving UHF partial discharge location based on the time-of-flight measurements, which are dependent on the accuracy with which the onset of PD signals can be determined. Wavelet de-noising is discussed in the context of how the resultant waveforms are modified in a way that alters the apparent arrival times. A method based on relative increase in energy is presented for determining the arrival times which might assist with PD location accuracy in high voltage equipment. In addition, possible approaches for implementing the relative increase in energy using automated systems in several ways are discussed.
Keywords :
partial discharges; power apparatus; signal denoising; time of flight spectra; time-of-arrival estimation; UHF partial discharge location; high voltage equipment; time-of-flight measurements; wavelet denoising; Acoustic signal detection; Degradation; Frequency; Insulation; Knee; Partial discharge measurement; Partial discharges; Sensor phenomena and characterization; UHF measurements; Voltage; UHF; partial discharge location;
Conference_Titel :
Universities Power Engineering Conference (UPEC), 2009 Proceedings of the 44th International
Conference_Location :
Glasgow
Print_ISBN :
978-1-4244-6823-2